PAT testing: how often is it needed? (UK)
The law does not require yearly PAT testing. HSE suggests starting intervals by type of equipment: earthed kettles and irons need inspecting every 6 to 12 months and testing every 1 to 2 years, while computers and photocopiers that are rarely moved need a visual check every 2 to 4 years.
Every check and its frequency
The HSE intervals are for low-risk workplaces such as offices, shops and hotels. Equipment used in tougher conditions needs checking more often.
| Check | How often | Basis | Status | Source |
|---|---|---|---|---|
| Class I (earthed) e.g. kettles, irons, some floor cleaners: formal visual inspection | Every 6 months to 1 year (suggested starting interval); user checks before use | Suggested starting intervals for low-risk workplaces from HSE leaflet INDG236. The law sets no testing frequency; adjust it in light of what your checks show. | Official guidance | HSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments checked |
| Class I (earthed) equipment: combined inspection and test (PAT) | Every 1 to 2 years (suggested starting interval) | HSE leaflet INDG236. PAT is not mandatory; for earthed equipment in low-risk workplaces, HSE suggests this as a starting interval. | Official guidance | HSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments checked |
| Class II hand-held (e.g. some floor cleaners, kitchen equipment): formal visual inspection | Every 6 months to 1 year; no PAT needed | Suggested starting interval in HSE leaflet INDG236 for hand-held equipment with double insulation. | Official guidance | HSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments checked |
| Class II not hand-held, moved occasionally (fans, table lamps): formal visual inspection | Every 2 to 4 years; no PAT needed | Suggested starting interval in HSE leaflet INDG236 for double-insulated equipment that seldom moves. | Official guidance | HSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments checked |
| Desktop computers, VDUs, photocopiers (rarely moved): formal visual inspection | Every 2 to 4 years; PAT none if double insulated, otherwise up to 5 years | Suggested starting interval in HSE leaflet INDG236 for office IT equipment and copiers that are seldom moved. | Official guidance | HSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments checked |
| Extension leads, cables, plugs, battery chargers: formal visual inspection and combined test | Visual every 6 months to 4 years; test every 1 to 5 years, depending on the connected equipment | HSE leaflet INDG236. Set the interval to suit the equipment the lead is used with. | Official guidance | HSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments checked |
The law does not require PAT testing every year. HSE's intervals are meant for low-risk workplaces; equipment used in harsh conditions (construction, workshops) needs checking more often.
What it is about
Portable appliance testing deals with electrical equipment that plugs into a socket, such as kettles, computers, extension leads, floor cleaners and power tools. The legal duty under the Electricity at Work Regulations is to maintain equipment so that it is safe, and HSE says this does not mean testing every item every year.
Most faults show up on a visual check: damaged cables, cracked plugs, burn marks and loose parts. HSE's suggested intervals vary with the type of equipment and how it is used; those given here are for low-risk workplaces such as offices, shops and hotels.
The checks one by one
Class I (earthed) e.g. kettles, irons, some floor cleaners: formal visual inspection
Every 6 months to 1 year (suggested starting interval); user checks before use · Official guidance
Suggested starting intervals for low-risk workplaces from HSE leaflet INDG236. The law sets no testing frequency; adjust it in light of what your checks show. Source, last checked .
Class I (earthed) equipment: combined inspection and test (PAT)
Every 1 to 2 years (suggested starting interval) · Official guidance
HSE leaflet INDG236. PAT is not mandatory; for earthed equipment in low-risk workplaces, HSE suggests this as a starting interval. Source, last checked .
Class II hand-held (e.g. some floor cleaners, kitchen equipment): formal visual inspection
Every 6 months to 1 year; no PAT needed · Official guidance
Suggested starting interval in HSE leaflet INDG236 for hand-held equipment with double insulation. Source, last checked .
Class II not hand-held, moved occasionally (fans, table lamps): formal visual inspection
Every 2 to 4 years; no PAT needed · Official guidance
Suggested starting interval in HSE leaflet INDG236 for double-insulated equipment that seldom moves. Source, last checked .
Desktop computers, VDUs, photocopiers (rarely moved): formal visual inspection
Every 2 to 4 years; PAT none if double insulated, otherwise up to 5 years · Official guidance
Suggested starting interval in HSE leaflet INDG236 for office IT equipment and copiers that are seldom moved. Source, last checked .
Extension leads, cables, plugs, battery chargers: formal visual inspection and combined test
Visual every 6 months to 4 years; test every 1 to 5 years, depending on the connected equipment · Official guidance
HSE leaflet INDG236. Set the interval to suit the equipment the lead is used with. Source, last checked .
Whose duty it is, and who can carry it out
The employer. According to HSE, a trained member of staff can do formal visual inspections, and anyone with suitable test equipment who can use it and understand the results can do a combined inspection and test. Neither has to be an electrician.
What to record
HSE says the law does not require equipment to be labelled or checks to be recorded. A register of equipment and inspection results is still good practice, and shows at a glance what is due.
How to run it well
- Ask people to look equipment over before using it, and to report anything damaged.
- Withdraw damaged equipment from use immediately.
- Maintain an equipment register, so nothing gets missed and intervals can be adjusted.
- Check more frequently where equipment works in harsh conditions, for example workshops or building sites.
- Look back over the results: where inspections seldom turn up faults, the intervals may be longer than you need.
Building types it applies to
Portable electrical equipment is included in our compliance calendar for every building type we cover. Every calendar puts it next to the other checks that building usually needs.
Managing it in software
A CAFM system can schedule these checks, remind the person responsible, and file every certificate or log entry against the asset, keeping the evidence together for an inspector or insurer. The table sets out what each product states in its documentation.
| Software | Compliance certificates and expiry tracking | Planned maintenance (PPM) scheduling | SFG20 maintenance library | Contractor portal | QR or NFC asset tags |
|---|---|---|---|---|---|
| Joblogic | Yes | Yes | Yes | Partly | Yes |
| Infraspeak | Yes | Yes | Yes | Yes | Yes |
| Planon | Partly | Yes | Yes | Partly | Yes |
| Concerto | Yes | Yes | Yes | Yes | Yes |
| Service Works Global | Partly | Yes | Yes | Partly | Yes |
| MaintainX | Partly | Yes | Not confirmed | Partly | Yes |
| Snapfix | Yes | Yes | Not confirmed | Partly | Partly |
For the products ordered for this job, see the top FM compliance software, or read what planned preventive maintenance is.
Common questions
Does the law require PAT testing every year?
No. The legal duty is to keep equipment in a safe condition. HSE's suggested intervals differ by equipment type and environment.
Do you need an electrician for PAT testing?
No. According to HSE, a trained member of staff can do visual inspections, and someone with the right equipment who knows how to use it can do the testing.
Does every item need testing?
No. According to HSE, double-insulated (Class II) equipment needs regular visual inspection but not a combined test.