PAT testing: how often is it needed? (UK)

The law does not require yearly PAT testing. HSE suggests starting intervals by type of equipment: earthed kettles and irons need inspecting every 6 to 12 months and testing every 1 to 2 years, while computers and photocopiers that are rarely moved need a visual check every 2 to 4 years.

Every check and its frequency

The HSE intervals are for low-risk workplaces such as offices, shops and hotels. Equipment used in tougher conditions needs checking more often.

CheckHow oftenBasisStatusSource
Class I (earthed) e.g. kettles, irons, some floor cleaners: formal visual inspectionEvery 6 months to 1 year (suggested starting interval); user checks before useSuggested starting intervals for low-risk workplaces from HSE leaflet INDG236. The law sets no testing frequency; adjust it in light of what your checks show.Official guidanceHSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments
checked
Class I (earthed) equipment: combined inspection and test (PAT)Every 1 to 2 years (suggested starting interval)HSE leaflet INDG236. PAT is not mandatory; for earthed equipment in low-risk workplaces, HSE suggests this as a starting interval.Official guidanceHSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments
checked
Class II hand-held (e.g. some floor cleaners, kitchen equipment): formal visual inspectionEvery 6 months to 1 year; no PAT neededSuggested starting interval in HSE leaflet INDG236 for hand-held equipment with double insulation.Official guidanceHSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments
checked
Class II not hand-held, moved occasionally (fans, table lamps): formal visual inspectionEvery 2 to 4 years; no PAT neededSuggested starting interval in HSE leaflet INDG236 for double-insulated equipment that seldom moves.Official guidanceHSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments
checked
Desktop computers, VDUs, photocopiers (rarely moved): formal visual inspectionEvery 2 to 4 years; PAT none if double insulated, otherwise up to 5 yearsSuggested starting interval in HSE leaflet INDG236 for office IT equipment and copiers that are seldom moved.Official guidanceHSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments
checked
Extension leads, cables, plugs, battery chargers: formal visual inspection and combined testVisual every 6 months to 4 years; test every 1 to 5 years, depending on the connected equipmentHSE leaflet INDG236. Set the interval to suit the equipment the lead is used with.Official guidanceHSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments
checked

The law does not require PAT testing every year. HSE's intervals are meant for low-risk workplaces; equipment used in harsh conditions (construction, workshops) needs checking more often.

What it is about

Portable appliance testing deals with electrical equipment that plugs into a socket, such as kettles, computers, extension leads, floor cleaners and power tools. The legal duty under the Electricity at Work Regulations is to maintain equipment so that it is safe, and HSE says this does not mean testing every item every year.

Most faults show up on a visual check: damaged cables, cracked plugs, burn marks and loose parts. HSE's suggested intervals vary with the type of equipment and how it is used; those given here are for low-risk workplaces such as offices, shops and hotels.

The checks one by one

Class I (earthed) e.g. kettles, irons, some floor cleaners: formal visual inspection

Every 6 months to 1 year (suggested starting interval); user checks before use · Official guidance

Suggested starting intervals for low-risk workplaces from HSE leaflet INDG236. The law sets no testing frequency; adjust it in light of what your checks show. Source, last checked .

Class I (earthed) equipment: combined inspection and test (PAT)

Every 1 to 2 years (suggested starting interval) · Official guidance

HSE leaflet INDG236. PAT is not mandatory; for earthed equipment in low-risk workplaces, HSE suggests this as a starting interval. Source, last checked .

Class II hand-held (e.g. some floor cleaners, kitchen equipment): formal visual inspection

Every 6 months to 1 year; no PAT needed · Official guidance

Suggested starting interval in HSE leaflet INDG236 for hand-held equipment with double insulation. Source, last checked .

Class II not hand-held, moved occasionally (fans, table lamps): formal visual inspection

Every 2 to 4 years; no PAT needed · Official guidance

Suggested starting interval in HSE leaflet INDG236 for double-insulated equipment that seldom moves. Source, last checked .

Desktop computers, VDUs, photocopiers (rarely moved): formal visual inspection

Every 2 to 4 years; PAT none if double insulated, otherwise up to 5 years · Official guidance

Suggested starting interval in HSE leaflet INDG236 for office IT equipment and copiers that are seldom moved. Source, last checked .

Extension leads, cables, plugs, battery chargers: formal visual inspection and combined test

Visual every 6 months to 4 years; test every 1 to 5 years, depending on the connected equipment · Official guidance

HSE leaflet INDG236. Set the interval to suit the equipment the lead is used with. Source, last checked .

Whose duty it is, and who can carry it out

The employer. According to HSE, a trained member of staff can do formal visual inspections, and anyone with suitable test equipment who can use it and understand the results can do a combined inspection and test. Neither has to be an electrician.

What to record

HSE says the law does not require equipment to be labelled or checks to be recorded. A register of equipment and inspection results is still good practice, and shows at a glance what is due.

How to run it well

  1. Ask people to look equipment over before using it, and to report anything damaged.
  2. Withdraw damaged equipment from use immediately.
  3. Maintain an equipment register, so nothing gets missed and intervals can be adjusted.
  4. Check more frequently where equipment works in harsh conditions, for example workshops or building sites.
  5. Look back over the results: where inspections seldom turn up faults, the intervals may be longer than you need.

Building types it applies to

Portable electrical equipment is included in our compliance calendar for every building type we cover. Every calendar puts it next to the other checks that building usually needs.

Managing it in software

A CAFM system can schedule these checks, remind the person responsible, and file every certificate or log entry against the asset, keeping the evidence together for an inspector or insurer. The table sets out what each product states in its documentation.

SoftwareCompliance certificates and expiry trackingPlanned maintenance (PPM) schedulingSFG20 maintenance libraryContractor portalQR or NFC asset tags
JoblogicYesYesYesPartlyYes
InfraspeakYesYesYesYesYes
PlanonPartlyYesYesPartlyYes
ConcertoYesYesYesYesYes
Service Works GlobalPartlyYesYesPartlyYes
MaintainXPartlyYesNot confirmedPartlyYes
SnapfixYesYesNot confirmedPartlyPartly

For the products ordered for this job, see the top FM compliance software, or read what planned preventive maintenance is.

Common questions

Does the law require PAT testing every year?

No. The legal duty is to keep equipment in a safe condition. HSE's suggested intervals differ by equipment type and environment.

Do you need an electrician for PAT testing?

No. According to HSE, a trained member of staff can do visual inspections, and someone with the right equipment who knows how to use it can do the testing.

Does every item need testing?

No. According to HSE, double-insulated (Class II) equipment needs regular visual inspection but not a combined test.

Other checks