How often do commercial premises need an EICR or fixed wire test? (UK)

Under the Electricity at Work Regulations the installation must be maintained, but no interval is set. For commercial premises NICEIC recommends an EICR at least every five years, and each report carries the inspector's date for the next one.

Every check and its frequency

Covers fixed electrical installations in workplaces in England, Wales and Scotland. A separate five-year legal requirement applies to rented homes in England.

CheckHow oftenBasisStatusSource
Maintain the fixed installation; inspect and test it often enough to prevent dangerNo interval set in law; the inspector recommends the next dateRegulation 4 of the Electricity at Work Regulations 1989. Electrical systems must by law be maintained to prevent danger, but no inspection interval is set.LawThe Electricity at Work Regulations 1989, regulation 4
checked
Periodic inspection and test (EICR) of commercial premisesAt least every 5 years (recommended)NICEIC recommends that business premises have an EICR at least every five years. This is a recommendation rather than law, and the inspector may set a shorter interval for your building.Official guidanceNICEIC: Electrical Installation Condition Reports (EICRs)
checked

Depending on how the building is used, how well it is maintained and its surroundings, your inspector may advise a shorter interval; work to the date on your most recent EICR. A separate legal five-year requirement applies to rented homes in England.

What it is about

Fixed wiring means the electrical installation built into the building: distribution boards, cables, sockets, switches and fixed lighting. An Electrical Installation Condition Report (EICR) records an inspection and test of that installation and recommends when the next one should take place.

Each defect is given a code: C1 for danger present, C2 for potentially dangerous, C3 for improvement recommended, and FI where further investigation is needed. Any C1, C2 or FI code makes the report unsatisfactory.

The checks one by one

Maintain the fixed installation; inspect and test it often enough to prevent danger

No interval set in law; the inspector recommends the next date · Law

Regulation 4 of the Electricity at Work Regulations 1989. Electrical systems must by law be maintained to prevent danger, but no inspection interval is set. Source, last checked .

Periodic inspection and test (EICR) of commercial premises

At least every 5 years (recommended) · Official guidance

NICEIC recommends that business premises have an EICR at least every five years. This is a recommendation rather than law, and the inspector may set a shorter interval for your building. Source, last checked .

Whose duty it is, and who can carry it out

The Electricity at Work Regulations 1989 require employers and anyone in control of an electrical system to maintain it, so far as is reasonably practicable, to prevent danger. A competent electrician should do the inspections, and many organisations use contractors registered with a scheme such as NICEIC.

What to record

No specific record is set in law, but keep every EICR along with evidence that its recommendations were dealt with. Between them, they are the main proof that the installation is maintained.

How to run it well

  1. Let the inspector reach every distribution board and area, or check that the report notes anything not inspected.
  2. Fix C1 defects immediately and C2 defects as a matter of urgency.
  3. Book the next inspection for the date given on the last report, which may be earlier than five years.
  4. Have a fresh inspection done after major alterations or a change in how the building is used.

Building types it applies to

Fixed electrical installation is included in our compliance calendar for every building type we cover. Every calendar puts it next to the other checks that building usually needs.

Managing it in software

A CAFM system can schedule these checks, remind the person responsible, and file every certificate or log entry against the asset, keeping the evidence together for an inspector or insurer. The table sets out what each product states in its documentation.

SoftwareCompliance certificates and expiry trackingPlanned maintenance (PPM) schedulingSFG20 maintenance libraryContractor portalQR or NFC asset tags
JoblogicYesYesYesPartlyYes
InfraspeakYesYesYesYesYes
PlanonPartlyYesYesPartlyYes
ConcertoYesYesYesYesYes
Service Works GlobalPartlyYesYesPartlyYes
MaintainXPartlyYesNot confirmedPartlyYes
SnapfixYesYesNot confirmedPartlyPartly

For the products ordered for this job, see the software for statutory compliance, or read what planned preventive maintenance is.

Common questions

Does the law require commercial premises to have an EICR every five years?

No. The legal duty is to maintain the installation; five years is the recommended maximum interval for commercial premises, and your inspector may set a shorter one.

When is an EICR unsatisfactory?

When it contains any C1 (danger present), C2 (potentially dangerous) or FI (further investigation) code.

Does the rented homes rule apply here too?

No. Rented homes in England are under a separate legal requirement to be inspected at least every five years.