How often are legionella risk assessments and water checks needed? (UK)

According to HSE, the law does not prescribe an annual or two-yearly review of the risk assessment; review it regularly and whenever something changes. HSE guidance sets the routine checks: sentinel outlet temperatures monthly, little-used outlets flushed weekly, cold tanks checked every six months and an annual tank inspection.

Every check and its frequency

Covers employers and people in control of premises, landlords included, whose water systems could expose people to legionella. The frequencies here are for hot and cold water systems, not cooling towers.

CheckHow oftenBasisStatusSource
Legionella risk assessment and its reviewRegularly; no fixed interval set in law. Also whenever it may no longer be validHSE guidance on the legal duty to assess and control the risk from legionella. No annual or two-yearly review is set in law; review regularly and whenever anything changes.LawHSE: Legionella and landlords' responsibilities
checked
Sentinel outlet temperature checks, hot and cold (cold <20C after 2 min; hot >=50C within 1 min)MonthlyHSE guidance on hot and cold water systems. Sentinel outlets are the taps closest to and furthest from each tank or cylinder.Official guidanceHSE: Hot and cold water systems - things to consider
checked
Calorifier flow and return temperatures (outgoing >=60C)MonthlyHSE guidance on hot and cold water systems. Stored hot water should be kept at 60°C or higher.Official guidanceHSE: Hot and cold water systems - things to consider
checked
TMV hot inlet temperature (>=50C within 1 min)MonthlyHSE guidance on hot and cold water systems, applying where thermostatic mixing valves are installed.Official guidanceHSE: Hot and cold water systems - things to consider
checked
Cold water storage tank temperature at ball valve outlet (<20C)Every 6 monthsHSE guidance on hot and cold water systems. Stored cold water should be kept under 20°C.Official guidanceHSE: Hot and cold water systems - things to consider
checked
Visual inspection and cleanliness check of cold water tanks and hot water cylindersAt least annuallyGuidance from HSE on hot and cold water systems.Official guidanceHSE: Hot and cold water systems - things to consider
checked
Flush infrequently used outletsWeeklyHSE guidance on hot and cold water systems. Avoid creating spray when flushing.Official guidanceHSE: Hot and cold water systems - things to consider
checked
Dismantle, clean and descale showerheads and hosesQuarterly, or as the risk assessment decidesHSE guidance on hot and cold water systems. Your risk assessment may set another interval.Official guidanceHSE: Hot and cold water systems - things to consider
checked
Check representative outlets on rotationRotational, so the whole system is covered (HSE page also says check annually for cold outlets)HSE guidance on hot and cold water systems. Pick outlets so that, over time, every part of the system is covered.Official guidanceHSE: Hot and cold water systems - things to consider
checked

These intervals are HSE guidance for typical hot and cold water systems, and your own risk assessment may set others. This list does not cover cooling towers or evaporative condensers.

What it is about

Legionella bacteria live in water and, when people breathe in small droplets of contaminated water, can cause Legionnaires' disease, a potentially fatal type of pneumonia. They grow best in water between about 20°C and 45°C, particularly where water is still or where scale, sludge or biofilm has built up.

This is why most routine checks focus on temperature: cold water kept cold, hot water kept hot, and water never left standing unused in pipes and outlets.

The checks one by one

Legionella risk assessment and its review

Regularly; no fixed interval set in law. Also whenever it may no longer be valid · Law

HSE guidance on the legal duty to assess and control the risk from legionella. No annual or two-yearly review is set in law; review regularly and whenever anything changes. Source, last checked .

Sentinel outlet temperature checks, hot and cold (cold <20C after 2 min; hot >=50C within 1 min)

Monthly · Official guidance

HSE guidance on hot and cold water systems. Sentinel outlets are the taps closest to and furthest from each tank or cylinder. Source, last checked .

Calorifier flow and return temperatures (outgoing >=60C)

Monthly · Official guidance

HSE guidance on hot and cold water systems. Stored hot water should be kept at 60°C or higher. Source, last checked .

TMV hot inlet temperature (>=50C within 1 min)

Monthly · Official guidance

HSE guidance on hot and cold water systems, applying where thermostatic mixing valves are installed. Source, last checked .

Cold water storage tank temperature at ball valve outlet (<20C)

Every 6 months · Official guidance

HSE guidance on hot and cold water systems. Stored cold water should be kept under 20°C. Source, last checked .

Visual inspection and cleanliness check of cold water tanks and hot water cylinders

At least annually · Official guidance

Guidance from HSE on hot and cold water systems. Source, last checked .

Flush infrequently used outlets

Weekly · Official guidance

HSE guidance on hot and cold water systems. Avoid creating spray when flushing. Source, last checked .

Dismantle, clean and descale showerheads and hoses

Quarterly, or as the risk assessment decides · Official guidance

HSE guidance on hot and cold water systems. Your risk assessment may set another interval. Source, last checked .

Check representative outlets on rotation

Rotational, so the whole system is covered (HSE page also says check annually for cold outlets) · Official guidance

HSE guidance on hot and cold water systems. Pick outlets so that, over time, every part of the system is covered. Source, last checked .

Whose duty it is, and who can carry it out

The dutyholder, meaning the employer or person in control of the premises, landlords included. They have to assess the risk and, where needed, put a scheme in place to control it. If they are not competent to do this themselves, they should appoint someone with the training, experience or knowledge to assist.

What to record

If you have five or more employees, record the significant findings of the risk assessment. HSE advises keeping records while they are current and for at least two years after that, and keeping monitoring records such as temperature checks for at least five years.

How to run it well

  1. Maintain a current drawing of the water system showing tanks, calorifiers and outlets.
  2. Where possible, remove pipework that no longer feeds an outlet, as water sits still in it.
  3. At least weekly, flush outlets in unused rooms such as empty offices or hotel bedrooms.
  4. Pick sentinel outlets (those nearest to and furthest from each tank or calorifier) and check their temperatures every month.
  5. Revisit the risk assessment after changes to the water system or to how the building is used.

Building types it applies to

Hot and cold water systems is included in our compliance calendar for every building type we cover. Every calendar puts it next to the other checks that building usually needs.

Managing it in software

A CAFM system can schedule these checks, remind the person responsible, and file every certificate or log entry against the asset, keeping the evidence together for an inspector or insurer. The table sets out what each product states in its documentation.

SoftwareCompliance certificates and expiry trackingPlanned maintenance (PPM) schedulingSFG20 maintenance libraryContractor portalQR or NFC asset tags
JoblogicYesYesYesPartlyYes
InfraspeakYesYesYesYesYes
PlanonPartlyYesYesPartlyYes
ConcertoYesYesYesYesYes
Service Works GlobalPartlyYesYesPartlyYes
MaintainXPartlyYesNot confirmedPartlyYes
SnapfixYesYesNot confirmedPartlyPartly

For the products ordered for this job, see the top FM compliance software, or read what planned preventive maintenance is.

Common questions

Does the law require a legionella risk assessment?

Yes. Employers and those in control of premises have to assess the risk from legionella. No fixed review date is set in law; review it regularly and whenever it may have stopped being valid.

How frequently should water temperatures be checked?

For hot and cold water systems, HSE guidance suggests monthly checks at sentinel outlets and calorifiers, and checks on cold water tanks every six months. Your own risk assessment may set other frequencies.

What temperatures are we looking for?

Per HSE guidance: cold water under 20°C after running for two minutes, hot water reaching at least 50°C within one minute, and water leaving the calorifier at no less than 60°C.

Are cooling towers covered by these checks?

No. Cooling towers and evaporative condensers have separate, stricter requirements that this page does not cover.