Emergency lighting testing: how often is it needed? (UK, 2026)

Run a brief functional test each month and a full rated-duration test once a year, and if the building has a central battery system, look at its indicators every day. BS 5266-1 and government fire safety guidance set these intervals; what the law itself requires is that the system is maintained.

Every check and its frequency

Covers any premises within the Fire Safety Order that has emergency escape lighting fitted, meaning workplaces and the common parts of blocks of flats in England and Wales.

CheckHow oftenBasisStatusSource
Visual check of central battery / central power supply indicatorsDailyThe Home Office fire safety guide for offices and shops and the ICEL emergency lighting guide both recommend this. It covers central battery systems only, not self-contained fittings.Official guidanceFire safety risk assessment: offices and shops (Home Office guide, published 5 June 2006, last updated 12 September 2023, applies to England)
checked
Monthly functional testMonthlyBS 5266-1 recommends this (as summarised in ICEL's lighting industry guide), as does the Home Office fire safety guide. It is not law in itself; under the Fire Safety Order, emergency lighting must be maintained.British StandardICEL Emergency Lighting Guide (Lighting Industry Association)
checked
Annual full rated-duration testAnnuallyBS 5266-1 (as summarised by ICEL) and the Home Office fire safety guide recommend this. Schedule the test for a quiet period, as the batteries take about a day to recharge.British StandardICEL Emergency Lighting Guide (Lighting Industry Association)
checked
Photometric verification of the systemInitially, then at intervals not exceeding 5 yearsAdded in BS 5266-1:2025: at least every five years, confirm that the system still provides the light levels it was designed for. This is a recommendation in a British Standard, not law.British StandardNICEIC: BS 5266-1 Emergency lighting (summary of the 2025 revision)
checked

BS 5266-1 was updated in October 2025. Self-testing emergency lighting can run these tests on its own, but a person must still review and log the results.

What it is about

When the normal lighting fails, emergency escape lighting switches on by itself so that people can find the way out and see the exit signs, fire alarm call points and fire-fighting equipment. Self-contained fittings, each carrying its own battery, are the norm in most workplaces, while some larger buildings rely on a central battery system supplying every fitting.

Battery capacity drops with age, so a fitting that ran for its full rated duration when new may fall short a few years on. Testing at regular intervals tells you this before a power cut does.

The checks one by one

Visual check of central battery / central power supply indicators

Daily · Official guidance

The Home Office fire safety guide for offices and shops and the ICEL emergency lighting guide both recommend this. It covers central battery systems only, not self-contained fittings. Source, last checked .

Monthly functional test

Monthly · British Standard

BS 5266-1 recommends this (as summarised in ICEL's lighting industry guide), as does the Home Office fire safety guide. It is not law in itself; under the Fire Safety Order, emergency lighting must be maintained. Source, last checked .

Annual full rated-duration test

Annually · British Standard

BS 5266-1 (as summarised by ICEL) and the Home Office fire safety guide recommend this. Schedule the test for a quiet period, as the batteries take about a day to recharge. Source, last checked .

Photometric verification of the system

Initially, then at intervals not exceeding 5 years · British Standard

Added in BS 5266-1:2025: at least every five years, confirm that the system still provides the light levels it was designed for. This is a recommendation in a British Standard, not law. Source, last checked .

Whose duty it is, and who can carry it out

Under the Fire Safety Order, the responsible person (usually the employer or whoever controls the premises) has to keep emergency lighting maintained. According to the ICEL guide, a competent person should be appointed to oversee testing, while the Home Office guide says trained staff can carry out routine monthly tests in-house. Many buildings bring in a specialist contractor for the annual full-duration test and for photometric verification.

What to record

An emergency lighting log book should record the date of each test, its results, any faults found and the date each fault was fixed. The ICEL guide says the fire authority should be able to inspect the log book. Self-testing systems carry out the tests automatically, but a person still has to check the results and record them.

How to run it well

  1. Give each fitting a number and mark it on a plan, so that faults can be logged against the right fitting.
  2. For the monthly test, use a test key switch instead of turning off the lighting circuit at the distribution board.
  3. Schedule the annual full-duration test for a time when the building can cope while the batteries recharge, such as the end of the working day.
  4. Change failed batteries and lamps without delay, and note the repair date in the log book.
  5. Recheck the system whenever the building layout changes, as escape routes may now be in different places.

Building types it applies to

Emergency escape lighting is included in our compliance calendar for every building type we cover. Every calendar puts it next to the other checks that building usually needs.

Managing it in software

A CAFM system can schedule these checks, remind the person responsible, and file every certificate or log entry against the asset, keeping the evidence together for an inspector or insurer. The table sets out what each product states in its documentation.

SoftwareCompliance certificates and expiry trackingPlanned maintenance (PPM) schedulingSFG20 maintenance libraryContractor portalQR or NFC asset tags
JoblogicYesYesYesPartlyYes
InfraspeakYesYesYesYesYes
PlanonPartlyYesYesPartlyYes
ConcertoYesYesYesYesYes
Service Works GlobalPartlyYesYesPartlyYes
MaintainXPartlyYesNot confirmedPartlyYes
SnapfixYesYesNot confirmedPartlyPartly

For the products ordered for this job, see the the compliance software shortlist, or read what planned preventive maintenance is.

Common questions

Does the law require emergency lighting to be tested?

Under the Fire Safety Order, emergency lighting must be maintained. BS 5266-1 and government guidance supply the test frequencies, and keeping to them is the normal way to demonstrate the system is maintained.

Can the monthly test be done by our own staff?

Yes. According to the Home Office guide, routine tests can be carried out in-house, provided the person knows what to look for and records what they find.

How long does the yearly test run for?

For the system's full rated duration, as marked on the fittings or given in the system documentation.

If fittings test themselves, are checks still needed?

Yes. The fittings run the tests automatically, but a person still has to review the results and enter them in the log book.