UK compliance calendar for a school
A school with a platform lift, kitchens, science labs and gas-fired heating.
Assets assumed: Fire risk assessment, Fire detection and alarm system, Emergency escape lighting, Fire doors, Hot and cold water systems, Fixed electrical installation, Portable electrical equipment, Lifting equipment, Gas appliances, installation pipework and flues.
| Check | How often | Basis | Status | Source |
|---|---|---|---|---|
| Fire risk assessment Review the fire risk assessment | Regularly; no fixed interval set in law. Also whenever it may no longer be valid or there has been a significant change | Article 9 of the Regulatory Reform (Fire Safety) Order 2005, as amended by the Building Safety Act 2022. Regular review is a legal requirement, but no fixed interval is set; each assessment and review has to be recorded in full. | Law | The Regulatory Reform (Fire Safety) Order 2005, article 9 checked |
| Fire detection and alarm system Check control and indicating equipment for faults | Daily (at least every 24 hours) | Section 2.5 of the Home Office fire safety guide for offices and shops. This is guidance; under the Fire Safety Order the system must be maintained. | Official guidance | Fire safety risk assessment: offices and shops (Home Office guide, published 5 June 2006, last updated 12 September 2023, applies to England) checked |
| Fire detection and alarm system Weekly alarm test (operate a different manual call point each week) | Weekly | BS 5839-1 and section 2.5 of the Home Office fire safety guide recommend this. Test a different call point each week and note which one you used. | British Standard | Fire safety risk assessment: offices and shops (Home Office guide, published 5 June 2006, last updated 12 September 2023, applies to England) checked |
| Fire detection and alarm system Inspection and servicing by a competent person | About every 6 months (any time 5 to 7 months after the last visit) | BS 5839-1:2025 recommends this, as summarised by the Fire Industry Association. A visit falling anywhere from five to seven months after the previous one is acceptable. | British Standard | Fire Industry Association: Guide to the changes in BS 5839-1:2025 checked |
| Emergency escape lighting Visual check of central battery / central power supply indicators | Daily | The Home Office fire safety guide for offices and shops and the ICEL emergency lighting guide both recommend this. It covers central battery systems only, not self-contained fittings. | Official guidance | Fire safety risk assessment: offices and shops (Home Office guide, published 5 June 2006, last updated 12 September 2023, applies to England) checked |
| Emergency escape lighting Monthly functional test | Monthly | BS 5266-1 recommends this (as summarised in ICEL's lighting industry guide), as does the Home Office fire safety guide. It is not law in itself; under the Fire Safety Order, emergency lighting must be maintained. | British Standard | ICEL Emergency Lighting Guide (Lighting Industry Association) checked |
| Emergency escape lighting Annual full rated-duration test | Annually | BS 5266-1 (as summarised by ICEL) and the Home Office fire safety guide recommend this. Schedule the test for a quiet period, as the batteries take about a day to recharge. | British Standard | ICEL Emergency Lighting Guide (Lighting Industry Association) checked |
| Emergency escape lighting Photometric verification of the system | Initially, then at intervals not exceeding 5 years | Added in BS 5266-1:2025: at least every five years, confirm that the system still provides the light levels it was designed for. This is a recommendation in a British Standard, not law. | British Standard | NICEIC: BS 5266-1 Emergency lighting (summary of the 2025 revision) checked |
| Fire doors Workplaces: check fire doors, seals and self-closers work correctly | Monthly (recommended) | Maintenance checklist in the Home Office fire safety guide for offices and shops. This is guidance; under the Fire Safety Order fire doors must be maintained. | Official guidance | Fire safety risk assessment: offices and shops (Home Office guide, published 5 June 2006, last updated 12 September 2023, applies to England) checked |
| Fire doors Workplaces: test release and closing mechanisms of fire-resisting compartment doors and shutters | Six-monthly (recommended) | Maintenance checklist in the Home Office fire safety guide for offices and shops. This is guidance, and the work should be done by a competent person. | Official guidance | Fire safety risk assessment: offices and shops (Home Office guide, published 5 June 2006, last updated 12 September 2023, applies to England) checked |
| Hot and cold water systems (legionella control) Legionella risk assessment and its review | Regularly; no fixed interval set in law. Also whenever it may no longer be valid | HSE guidance on the legal duty to assess and control the risk from legionella. No annual or two-yearly review is set in law; review regularly and whenever anything changes. | Law | HSE: Legionella and landlords' responsibilities checked |
| Hot and cold water systems (legionella control) Sentinel outlet temperature checks, hot and cold (cold <20C after 2 min; hot >=50C within 1 min) | Monthly | HSE guidance on hot and cold water systems. Sentinel outlets are the taps closest to and furthest from each tank or cylinder. | Official guidance | HSE: Hot and cold water systems - things to consider checked |
| Hot and cold water systems (legionella control) Calorifier flow and return temperatures (outgoing >=60C) | Monthly | HSE guidance on hot and cold water systems. Stored hot water should be kept at 60°C or higher. | Official guidance | HSE: Hot and cold water systems - things to consider checked |
| Hot and cold water systems (legionella control) TMV hot inlet temperature (>=50C within 1 min) | Monthly | HSE guidance on hot and cold water systems, applying where thermostatic mixing valves are installed. | Official guidance | HSE: Hot and cold water systems - things to consider checked |
| Hot and cold water systems (legionella control) Cold water storage tank temperature at ball valve outlet (<20C) | Every 6 months | HSE guidance on hot and cold water systems. Stored cold water should be kept under 20°C. | Official guidance | HSE: Hot and cold water systems - things to consider checked |
| Hot and cold water systems (legionella control) Visual inspection and cleanliness check of cold water tanks and hot water cylinders | At least annually | Guidance from HSE on hot and cold water systems. | Official guidance | HSE: Hot and cold water systems - things to consider checked |
| Hot and cold water systems (legionella control) Flush infrequently used outlets | Weekly | HSE guidance on hot and cold water systems. Avoid creating spray when flushing. | Official guidance | HSE: Hot and cold water systems - things to consider checked |
| Hot and cold water systems (legionella control) Dismantle, clean and descale showerheads and hoses | Quarterly, or as the risk assessment decides | HSE guidance on hot and cold water systems. Your risk assessment may set another interval. | Official guidance | HSE: Hot and cold water systems - things to consider checked |
| Hot and cold water systems (legionella control) Check representative outlets on rotation | Rotational, so the whole system is covered (HSE page also says check annually for cold outlets) | HSE guidance on hot and cold water systems. Pick outlets so that, over time, every part of the system is covered. | Official guidance | HSE: Hot and cold water systems - things to consider checked |
| Fixed electrical installation (EICR) in workplaces Maintain the fixed installation; inspect and test it often enough to prevent danger | No interval set in law; the inspector recommends the next date | Regulation 4 of the Electricity at Work Regulations 1989. Electrical systems must by law be maintained to prevent danger, but no inspection interval is set. | Law | The Electricity at Work Regulations 1989, regulation 4 checked |
| Fixed electrical installation (EICR) in workplaces Periodic inspection and test (EICR) of commercial premises | At least every 5 years (recommended) | NICEIC recommends that business premises have an EICR at least every five years. This is a recommendation rather than law, and the inspector may set a shorter interval for your building. | Official guidance | NICEIC: Electrical Installation Condition Reports (EICRs) checked |
| Portable electrical equipment (PAT) Class I (earthed) e.g. kettles, irons, some floor cleaners: formal visual inspection | Every 6 months to 1 year (suggested starting interval); user checks before use | Suggested starting intervals for low-risk workplaces from HSE leaflet INDG236. The law sets no testing frequency; adjust it in light of what your checks show. | Official guidance | HSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments checked |
| Portable electrical equipment (PAT) Class I (earthed) equipment: combined inspection and test (PAT) | Every 1 to 2 years (suggested starting interval) | HSE leaflet INDG236. PAT is not mandatory; for earthed equipment in low-risk workplaces, HSE suggests this as a starting interval. | Official guidance | HSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments checked |
| Portable electrical equipment (PAT) Class II hand-held (e.g. some floor cleaners, kitchen equipment): formal visual inspection | Every 6 months to 1 year; no PAT needed | Suggested starting interval in HSE leaflet INDG236 for hand-held equipment with double insulation. | Official guidance | HSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments checked |
| Portable electrical equipment (PAT) Class II not hand-held, moved occasionally (fans, table lamps): formal visual inspection | Every 2 to 4 years; no PAT needed | Suggested starting interval in HSE leaflet INDG236 for double-insulated equipment that seldom moves. | Official guidance | HSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments checked |
| Portable electrical equipment (PAT) Desktop computers, VDUs, photocopiers (rarely moved): formal visual inspection | Every 2 to 4 years; PAT none if double insulated, otherwise up to 5 years | Suggested starting interval in HSE leaflet INDG236 for office IT equipment and copiers that are seldom moved. | Official guidance | HSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments checked |
| Portable electrical equipment (PAT) Extension leads, cables, plugs, battery chargers: formal visual inspection and combined test | Visual every 6 months to 4 years; test every 1 to 5 years, depending on the connected equipment | HSE leaflet INDG236. Set the interval to suit the equipment the lead is used with. | Official guidance | HSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments checked |
| Lifting equipment (passenger/goods lifts, hoists, lifting accessories) Thorough examination: equipment for lifting people, and lifting accessories | At least every 6 months (or as set by an examination scheme) | Regulation 9 of the Lifting Operations and Lifting Equipment Regulations 1998. Required by law for passenger lifts and lifting accessories, except where a written examination scheme sets a different interval. | Law | The Lifting Operations and Lifting Equipment Regulations 1998, regulation 9 checked |
| Lifting equipment (passenger/goods lifts, hoists, lifting accessories) Thorough examination: other lifting equipment (e.g. goods lifts) | At least every 12 months (or as set by an examination scheme) | Regulation 9 of the Lifting Operations and Lifting Equipment Regulations 1998. Required by law, except where a written examination scheme sets a different interval. | Law | The Lifting Operations and Lifting Equipment Regulations 1998, regulation 9 checked |
| Lifting equipment (passenger/goods lifts, hoists, lifting accessories) Inspection between thorough examinations | At suitable intervals, where appropriate (no fixed frequency) | Regulation 9 of the Lifting Operations and Lifting Equipment Regulations 1998. Required where appropriate, at intervals that a competent person considers suitable. | Law | The Lifting Operations and Lifting Equipment Regulations 1998, regulation 9 checked |
| Gas appliances, installation pipework and flues Workplaces: maintain gas appliances, pipework and flues in a safe condition | No fixed legal frequency for workplaces | Regulation 35 of the Gas Safety (Installation and Use) Regulations 1998. Employers have to keep gas appliances, pipework and flues safe to use; for workplaces, the law sets no fixed check interval. | Law | The Gas Safety (Installation and Use) Regulations 1998, regulation 35 checked |
England unless stated. Where the law sets a duty without an interval, the row says so; a recommended frequency is the one an inspector or insurer will usually look for.