UK compliance calendar for a office

An office over several floors, with a passenger lift, air conditioning, gas-fired heating and kitchens for staff.

Assets assumed: Fire risk assessment, Fire detection and alarm system, Emergency escape lighting, Fire doors, Hot and cold water systems, Fixed electrical installation, Portable electrical equipment, Lifting equipment, Air-conditioning systems, Equipment containing fluorinated greenhouse gases, Gas appliances, installation pipework and flues.

CheckHow oftenBasisStatusSource
Fire risk assessment
Review the fire risk assessment
Regularly; no fixed interval set in law. Also whenever it may no longer be valid or there has been a significant changeArticle 9 of the Regulatory Reform (Fire Safety) Order 2005, as amended by the Building Safety Act 2022. Regular review is a legal requirement, but no fixed interval is set; each assessment and review has to be recorded in full.LawThe Regulatory Reform (Fire Safety) Order 2005, article 9
checked
Fire detection and alarm system
Check control and indicating equipment for faults
Daily (at least every 24 hours)Section 2.5 of the Home Office fire safety guide for offices and shops. This is guidance; under the Fire Safety Order the system must be maintained.Official guidanceFire safety risk assessment: offices and shops (Home Office guide, published 5 June 2006, last updated 12 September 2023, applies to England)
checked
Fire detection and alarm system
Weekly alarm test (operate a different manual call point each week)
WeeklyBS 5839-1 and section 2.5 of the Home Office fire safety guide recommend this. Test a different call point each week and note which one you used.British StandardFire safety risk assessment: offices and shops (Home Office guide, published 5 June 2006, last updated 12 September 2023, applies to England)
checked
Fire detection and alarm system
Inspection and servicing by a competent person
About every 6 months (any time 5 to 7 months after the last visit)BS 5839-1:2025 recommends this, as summarised by the Fire Industry Association. A visit falling anywhere from five to seven months after the previous one is acceptable.British StandardFire Industry Association: Guide to the changes in BS 5839-1:2025
checked
Emergency escape lighting
Visual check of central battery / central power supply indicators
DailyThe Home Office fire safety guide for offices and shops and the ICEL emergency lighting guide both recommend this. It covers central battery systems only, not self-contained fittings.Official guidanceFire safety risk assessment: offices and shops (Home Office guide, published 5 June 2006, last updated 12 September 2023, applies to England)
checked
Emergency escape lighting
Monthly functional test
MonthlyBS 5266-1 recommends this (as summarised in ICEL's lighting industry guide), as does the Home Office fire safety guide. It is not law in itself; under the Fire Safety Order, emergency lighting must be maintained.British StandardICEL Emergency Lighting Guide (Lighting Industry Association)
checked
Emergency escape lighting
Annual full rated-duration test
AnnuallyBS 5266-1 (as summarised by ICEL) and the Home Office fire safety guide recommend this. Schedule the test for a quiet period, as the batteries take about a day to recharge.British StandardICEL Emergency Lighting Guide (Lighting Industry Association)
checked
Emergency escape lighting
Photometric verification of the system
Initially, then at intervals not exceeding 5 yearsAdded in BS 5266-1:2025: at least every five years, confirm that the system still provides the light levels it was designed for. This is a recommendation in a British Standard, not law.British StandardNICEIC: BS 5266-1 Emergency lighting (summary of the 2025 revision)
checked
Fire doors
Workplaces: check fire doors, seals and self-closers work correctly
Monthly (recommended)Maintenance checklist in the Home Office fire safety guide for offices and shops. This is guidance; under the Fire Safety Order fire doors must be maintained.Official guidanceFire safety risk assessment: offices and shops (Home Office guide, published 5 June 2006, last updated 12 September 2023, applies to England)
checked
Fire doors
Workplaces: test release and closing mechanisms of fire-resisting compartment doors and shutters
Six-monthly (recommended)Maintenance checklist in the Home Office fire safety guide for offices and shops. This is guidance, and the work should be done by a competent person.Official guidanceFire safety risk assessment: offices and shops (Home Office guide, published 5 June 2006, last updated 12 September 2023, applies to England)
checked
Hot and cold water systems (legionella control)
Legionella risk assessment and its review
Regularly; no fixed interval set in law. Also whenever it may no longer be validHSE guidance on the legal duty to assess and control the risk from legionella. No annual or two-yearly review is set in law; review regularly and whenever anything changes.LawHSE: Legionella and landlords' responsibilities
checked
Hot and cold water systems (legionella control)
Sentinel outlet temperature checks, hot and cold (cold <20C after 2 min; hot >=50C within 1 min)
MonthlyHSE guidance on hot and cold water systems. Sentinel outlets are the taps closest to and furthest from each tank or cylinder.Official guidanceHSE: Hot and cold water systems - things to consider
checked
Hot and cold water systems (legionella control)
Calorifier flow and return temperatures (outgoing >=60C)
MonthlyHSE guidance on hot and cold water systems. Stored hot water should be kept at 60°C or higher.Official guidanceHSE: Hot and cold water systems - things to consider
checked
Hot and cold water systems (legionella control)
TMV hot inlet temperature (>=50C within 1 min)
MonthlyHSE guidance on hot and cold water systems, applying where thermostatic mixing valves are installed.Official guidanceHSE: Hot and cold water systems - things to consider
checked
Hot and cold water systems (legionella control)
Cold water storage tank temperature at ball valve outlet (<20C)
Every 6 monthsHSE guidance on hot and cold water systems. Stored cold water should be kept under 20°C.Official guidanceHSE: Hot and cold water systems - things to consider
checked
Hot and cold water systems (legionella control)
Visual inspection and cleanliness check of cold water tanks and hot water cylinders
At least annuallyGuidance from HSE on hot and cold water systems.Official guidanceHSE: Hot and cold water systems - things to consider
checked
Hot and cold water systems (legionella control)
Flush infrequently used outlets
WeeklyHSE guidance on hot and cold water systems. Avoid creating spray when flushing.Official guidanceHSE: Hot and cold water systems - things to consider
checked
Hot and cold water systems (legionella control)
Dismantle, clean and descale showerheads and hoses
Quarterly, or as the risk assessment decidesHSE guidance on hot and cold water systems. Your risk assessment may set another interval.Official guidanceHSE: Hot and cold water systems - things to consider
checked
Hot and cold water systems (legionella control)
Check representative outlets on rotation
Rotational, so the whole system is covered (HSE page also says check annually for cold outlets)HSE guidance on hot and cold water systems. Pick outlets so that, over time, every part of the system is covered.Official guidanceHSE: Hot and cold water systems - things to consider
checked
Fixed electrical installation (EICR) in workplaces
Maintain the fixed installation; inspect and test it often enough to prevent danger
No interval set in law; the inspector recommends the next dateRegulation 4 of the Electricity at Work Regulations 1989. Electrical systems must by law be maintained to prevent danger, but no inspection interval is set.LawThe Electricity at Work Regulations 1989, regulation 4
checked
Fixed electrical installation (EICR) in workplaces
Periodic inspection and test (EICR) of commercial premises
At least every 5 years (recommended)NICEIC recommends that business premises have an EICR at least every five years. This is a recommendation rather than law, and the inspector may set a shorter interval for your building.Official guidanceNICEIC: Electrical Installation Condition Reports (EICRs)
checked
Portable electrical equipment (PAT)
Class I (earthed) e.g. kettles, irons, some floor cleaners: formal visual inspection
Every 6 months to 1 year (suggested starting interval); user checks before useSuggested starting intervals for low-risk workplaces from HSE leaflet INDG236. The law sets no testing frequency; adjust it in light of what your checks show.Official guidanceHSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments
checked
Portable electrical equipment (PAT)
Class I (earthed) equipment: combined inspection and test (PAT)
Every 1 to 2 years (suggested starting interval)HSE leaflet INDG236. PAT is not mandatory; for earthed equipment in low-risk workplaces, HSE suggests this as a starting interval.Official guidanceHSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments
checked
Portable electrical equipment (PAT)
Class II hand-held (e.g. some floor cleaners, kitchen equipment): formal visual inspection
Every 6 months to 1 year; no PAT neededSuggested starting interval in HSE leaflet INDG236 for hand-held equipment with double insulation.Official guidanceHSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments
checked
Portable electrical equipment (PAT)
Class II not hand-held, moved occasionally (fans, table lamps): formal visual inspection
Every 2 to 4 years; no PAT neededSuggested starting interval in HSE leaflet INDG236 for double-insulated equipment that seldom moves.Official guidanceHSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments
checked
Portable electrical equipment (PAT)
Desktop computers, VDUs, photocopiers (rarely moved): formal visual inspection
Every 2 to 4 years; PAT none if double insulated, otherwise up to 5 yearsSuggested starting interval in HSE leaflet INDG236 for office IT equipment and copiers that are seldom moved.Official guidanceHSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments
checked
Portable electrical equipment (PAT)
Extension leads, cables, plugs, battery chargers: formal visual inspection and combined test
Visual every 6 months to 4 years; test every 1 to 5 years, depending on the connected equipmentHSE leaflet INDG236. Set the interval to suit the equipment the lead is used with.Official guidanceHSE INDG236(rev3): Maintaining portable electrical equipment in low-risk environments
checked
Lifting equipment (passenger/goods lifts, hoists, lifting accessories)
Thorough examination: equipment for lifting people, and lifting accessories
At least every 6 months (or as set by an examination scheme)Regulation 9 of the Lifting Operations and Lifting Equipment Regulations 1998. Required by law for passenger lifts and lifting accessories, except where a written examination scheme sets a different interval.LawThe Lifting Operations and Lifting Equipment Regulations 1998, regulation 9
checked
Lifting equipment (passenger/goods lifts, hoists, lifting accessories)
Thorough examination: other lifting equipment (e.g. goods lifts)
At least every 12 months (or as set by an examination scheme)Regulation 9 of the Lifting Operations and Lifting Equipment Regulations 1998. Required by law, except where a written examination scheme sets a different interval.LawThe Lifting Operations and Lifting Equipment Regulations 1998, regulation 9
checked
Lifting equipment (passenger/goods lifts, hoists, lifting accessories)
Inspection between thorough examinations
At suitable intervals, where appropriate (no fixed frequency)Regulation 9 of the Lifting Operations and Lifting Equipment Regulations 1998. Required where appropriate, at intervals that a competent person considers suitable.LawThe Lifting Operations and Lifting Equipment Regulations 1998, regulation 9
checked
Air-conditioning systems (TM44 inspection)
Inspection of accessible parts of the system by an energy assessor
At regular intervals not exceeding 5 yearsRegulation 18 of the Energy Performance of Buildings (England and Wales) Regulations 2012. Required by law for air-conditioning systems above 12 kW.LawThe Energy Performance of Buildings (England and Wales) Regulations 2012, Part 4
checked
Equipment containing fluorinated greenhouse gases (refrigeration, air-conditioning, heat pumps, fire protection, switchgear)
Leak check: 5 to <50 tonnes CO2e
At least every 12 months (24 months with a leak detection system)Article 4 of the F-gas Regulation (as it applies in Great Britain). Required by law and done by a certified technician.LawRegulation (EU) No 517/2014 as retained in GB law, article 4
checked
Equipment containing fluorinated greenhouse gases (refrigeration, air-conditioning, heat pumps, fire protection, switchgear)
Leak check: 50 to <500 tonnes CO2e
At least every 6 months (12 months with a leak detection system)Article 4 of the F-gas Regulation (as it applies in Great Britain). Required by law and done by a certified technician.LawRegulation (EU) No 517/2014 as retained in GB law, article 4
checked
Equipment containing fluorinated greenhouse gases (refrigeration, air-conditioning, heat pumps, fire protection, switchgear)
Leak check: 500 tonnes CO2e or more
At least every 3 months (6 months with a leak detection system)Article 4 of the F-gas Regulation (as it applies in Great Britain). Equipment of this size also needs an automatic leak detection system, which must be checked every year.LawRegulation (EU) No 517/2014 as retained in GB law, article 4
checked
Equipment containing fluorinated greenhouse gases (refrigeration, air-conditioning, heat pumps, fire protection, switchgear)
After a leak is found: repair as soon as possible and re-test
Re-test within 1 month of repairGuidance on GOV.UK from the Environment Agency and Defra about the F-gas rules. Failing to repair leaks is against the law and can result in a civil penalty.LawGOV.UK: Checking F gas equipment for leaks (Environment Agency / Defra)
checked
Gas appliances, installation pipework and flues
Workplaces: maintain gas appliances, pipework and flues in a safe condition
No fixed legal frequency for workplacesRegulation 35 of the Gas Safety (Installation and Use) Regulations 1998. Employers have to keep gas appliances, pipework and flues safe to use; for workplaces, the law sets no fixed check interval.LawThe Gas Safety (Installation and Use) Regulations 1998, regulation 35
checked

England unless stated. Where the law sets a duty without an interval, the row says so; a recommended frequency is the one an inspector or insurer will usually look for.