F-gas leak checks in Great Britain: thresholds and how often
A leak check is needed at least every 12 months for equipment holding 5 to 50 tonnes CO2 equivalent, every 6 months for 50 to 500 tonnes, and every 3 months for 500 tonnes or more. Each interval doubles if a leak detection system is fitted.
Every check and its frequency
Covers operators of refrigeration, air conditioning, heat pumps, fire protection and switchgear holding 5 tonnes CO2 equivalent or more of F-gas in England, Scotland and Wales. Different rules apply in Northern Ireland.
| Check | How often | Basis | Status | Source |
|---|---|---|---|---|
| Leak check: 5 to <50 tonnes CO2e | At least every 12 months (24 months with a leak detection system) | Article 4 of the F-gas Regulation (as it applies in Great Britain). Required by law and done by a certified technician. | Law | Regulation (EU) No 517/2014 as retained in GB law, article 4 checked |
| Leak check: 50 to <500 tonnes CO2e | At least every 6 months (12 months with a leak detection system) | Article 4 of the F-gas Regulation (as it applies in Great Britain). Required by law and done by a certified technician. | Law | Regulation (EU) No 517/2014 as retained in GB law, article 4 checked |
| Leak check: 500 tonnes CO2e or more | At least every 3 months (6 months with a leak detection system) | Article 4 of the F-gas Regulation (as it applies in Great Britain). Equipment of this size also needs an automatic leak detection system, which must be checked every year. | Law | Regulation (EU) No 517/2014 as retained in GB law, article 4 checked |
| After a leak is found: repair as soon as possible and re-test | Re-test within 1 month of repair | Guidance on GOV.UK from the Environment Agency and Defra about the F-gas rules. Failing to repair leaks is against the law and can result in a civil penalty. | Law | GOV.UK: Checking F gas equipment for leaks (Environment Agency / Defra) checked |
These rules cover England, Scotland and Wales. Northern Ireland follows the newer EU F-gas Regulation, whose thresholds differ. Thresholds are expressed in tonnes of CO2 equivalent, so ask your engineer to convert the refrigerant charge (for example, 2.4 kg of R410A equals 5 tonnes).
What it is about
Fluorinated greenhouse gases (F gases) serve as refrigerants in air-conditioning, refrigeration and heat pumps, and are also found in some fire protection systems and electrical switchgear. Because they are powerful greenhouse gases, the law requires larger systems to be leak checked regularly.
How often checks are needed depends on the size of the charge, measured in tonnes of CO2 equivalent instead of kilograms. As an example, 2.4 kg of R410A equals 5 tonnes of CO2 equivalent, which is the threshold where checks begin.
The checks one by one
Leak check: 5 to <50 tonnes CO2e
At least every 12 months (24 months with a leak detection system) · Law
Article 4 of the F-gas Regulation (as it applies in Great Britain). Required by law and done by a certified technician. Source, last checked .
Leak check: 50 to <500 tonnes CO2e
At least every 6 months (12 months with a leak detection system) · Law
Article 4 of the F-gas Regulation (as it applies in Great Britain). Required by law and done by a certified technician. Source, last checked .
Leak check: 500 tonnes CO2e or more
At least every 3 months (6 months with a leak detection system) · Law
Article 4 of the F-gas Regulation (as it applies in Great Britain). Equipment of this size also needs an automatic leak detection system, which must be checked every year. Source, last checked .
After a leak is found: repair as soon as possible and re-test
Re-test within 1 month of repair · Law
Guidance on GOV.UK from the Environment Agency and Defra about the F-gas rules. Failing to repair leaks is against the law and can result in a civil penalty. Source, last checked .
Whose duty it is, and who can carry it out
The equipment's operator, usually whoever controls how it runs. Leak checks have to be done by technicians certified for that kind of equipment.
What to record
Operators also have record-keeping duties under the regulations. Have your engineer record every leak check, every repair and any refrigerant added or recovered, and store the records with the equipment's documentation.
How to run it well
- Make a list of every system containing F gas, with its refrigerant type and charge, and have your engineer convert each charge into tonnes of CO2 equivalent.
- Find out whether a leak detection system is installed, as it halves how often checks are required.
- Ensure leaks are fixed as soon as possible and the system is checked again within a month of the repair.
- Treat F-gas leak checks and TM44 energy inspections separately: they are different duties.
Building types it applies to
Equipment containing fluorinated greenhouse gases is included in our compliance calendar for 4 of the 5 building types on the site. Every calendar puts it next to the other checks that building usually needs.
Managing it in software
A CAFM system can schedule these checks, remind the person responsible, and file every certificate or log entry against the asset, keeping the evidence together for an inspector or insurer. The table sets out what each product states in its documentation.
| Software | Compliance certificates and expiry tracking | Planned maintenance (PPM) scheduling | SFG20 maintenance library | Contractor portal | QR or NFC asset tags |
|---|---|---|---|---|---|
| Joblogic | Yes | Yes | Yes | Partly | Yes |
| Infraspeak | Yes | Yes | Yes | Yes | Yes |
| Planon | Partly | Yes | Yes | Partly | Yes |
| Concerto | Yes | Yes | Yes | Yes | Yes |
| Service Works Global | Partly | Yes | Yes | Partly | Yes |
| MaintainX | Partly | Yes | Not confirmed | Partly | Yes |
| Snapfix | Yes | Yes | Not confirmed | Partly | Partly |
For the products ordered for this job, see the top FM compliance software, or read what planned preventive maintenance is.
Common questions
What systems need F-gas leak checks?
Among others, stationary refrigeration, air-conditioning, heat pump and fire protection equipment holding 5 tonnes of CO2 equivalent or more of F gas.
How frequently are leak checks required?
Anything from every 12 months for smaller systems to every three months for the biggest, with the interval doubled if a leak detection system is fitted.
Do these rules apply in Northern Ireland?
Northern Ireland follows the newer EU F-gas Regulation, which has different thresholds. This page covers the rules for England, Scotland and Wales.