How often must fire doors be inspected, and when is it a legal duty? (UK)

In England, blocks of flats taller than 11 metres must have communal fire doors checked at least once every three months and flat entrance doors once a year. For other buildings the law sets no interval, and government guidance recommends checking doors, seals and closers monthly.

Every check and its frequency

The quarterly and annual checks are a legal requirement only in England, in buildings over 11 metres tall that contain two or more flats. Other premises have to keep fire doors maintained under the Fire Safety Order.

CheckHow oftenBasisStatusSource
Check fire doors in communal areas, including that self-closing devices workAt least every 3 monthsRegulation 10 of the Fire Safety (England) Regulations 2022. Required by law for blocks of flats in England that are over 11 metres tall.LawThe Fire Safety (England) Regulations 2022, regulation 10 (as made)
checked
Use best endeavours to check flat entrance fire doors, including self-closersAt least every 12 monthsRegulation 10 of the Fire Safety (England) Regulations 2022. Required by law for blocks of flats over 11 metres; you must make every reasonable effort to get access and keep a record of your attempts.LawThe Fire Safety (England) Regulations 2022, regulation 10 (as made)
checked
Give residents fire door information (keep shut, do not tamper with self-closers, report faults)On move-in and at least every 12 monthsRegulation 10 of the Fire Safety (England) Regulations 2022. This applies to every block of flats with shared escape routes, regardless of height.LawThe Fire Safety (England) Regulations 2022, regulation 10 (as made)
checked
Workplaces: check fire doors, seals and self-closers work correctlyMonthly (recommended)Maintenance checklist in the Home Office fire safety guide for offices and shops. This is guidance; under the Fire Safety Order fire doors must be maintained.Official guidanceFire safety risk assessment: offices and shops (Home Office guide, published 5 June 2006, last updated 12 September 2023, applies to England)
checked
Workplaces: test release and closing mechanisms of fire-resisting compartment doors and shuttersSix-monthly (recommended)Maintenance checklist in the Home Office fire safety guide for offices and shops. This is guidance, and the work should be done by a competent person.Official guidanceFire safety risk assessment: offices and shops (Home Office guide, published 5 June 2006, last updated 12 September 2023, applies to England)
checked

In law, the quarterly and annual door checks apply only to buildings in England that contain two or more flats and are over 11 metres tall (measured to the top storey). Fire doors in other buildings must still be maintained, but the law sets no fixed frequency for them.

What it is about

Fire doors hold back fire and smoke for a set period, protecting escape routes and splitting a building into compartments. They only work when closed: a door wedged open, a broken self-closer, missing seals or uneven gaps round the frame all cut the protection they provide.

The Fire Safety (England) Regulations 2022 fix check intervals for fire doors in English blocks of flats over 11 metres tall. All other buildings must still keep their fire doors maintained, at a frequency set by the fire risk assessment and government guidance.

The checks one by one

Check fire doors in communal areas, including that self-closing devices work

At least every 3 months · Law

Regulation 10 of the Fire Safety (England) Regulations 2022. Required by law for blocks of flats in England that are over 11 metres tall. Source, last checked .

Use best endeavours to check flat entrance fire doors, including self-closers

At least every 12 months · Law

Regulation 10 of the Fire Safety (England) Regulations 2022. Required by law for blocks of flats over 11 metres; you must make every reasonable effort to get access and keep a record of your attempts. Source, last checked .

Give residents fire door information (keep shut, do not tamper with self-closers, report faults)

On move-in and at least every 12 months · Law

Regulation 10 of the Fire Safety (England) Regulations 2022. This applies to every block of flats with shared escape routes, regardless of height. Source, last checked .

Workplaces: check fire doors, seals and self-closers work correctly

Monthly (recommended) · Official guidance

Maintenance checklist in the Home Office fire safety guide for offices and shops. This is guidance; under the Fire Safety Order fire doors must be maintained. Source, last checked .

Workplaces: test release and closing mechanisms of fire-resisting compartment doors and shutters

Six-monthly (recommended) · Official guidance

Maintenance checklist in the Home Office fire safety guide for offices and shops. This is guidance, and the work should be done by a competent person. Source, last checked .

Whose duty it is, and who can carry it out

It falls to the responsible person under the Fire Safety Order. For blocks of flats in England, the 2022 regulations add specific duties: checking communal fire doors and flat entrance doors in buildings over 11 metres, and giving residents information about fire doors where a building has two or more flats. In workplaces, nominated staff can do routine checks, while a competent person should test the release mechanisms on compartment doors and shutters.

What to record

In buildings over 11 metres, the regulations require a record of the steps taken to check flat entrance doors, including attempts to gain access where it was refused. In other buildings the law sets no specific record, but logging checks and repairs is the easiest way to show the doors are maintained.

How to run it well

  1. Make sure the door shuts fully into its frame and latches from any angle without sticking.
  2. Confirm intumescent strips and smoke seals are in place and undamaged.
  3. Make sure the hinges are secure and the gaps round the door look even.
  4. Look out for damage or alterations, for example holes, new locks or glazing added without the correct fire-rated parts.
  5. Do not wedge fire doors open; where a door has to stay open, ask about hold-open devices that release when the fire alarm goes off.

Building types it applies to

Fire doors is included in our compliance calendar for every building type we cover. Every calendar puts it next to the other checks that building usually needs.

Managing it in software

A CAFM system can schedule these checks, remind the person responsible, and file every certificate or log entry against the asset, keeping the evidence together for an inspector or insurer. The table sets out what each product states in its documentation.

SoftwareCompliance certificates and expiry trackingPlanned maintenance (PPM) schedulingSFG20 maintenance libraryContractor portalQR or NFC asset tags
JoblogicYesYesYesPartlyYes
InfraspeakYesYesYesYesYes
PlanonPartlyYesYesPartlyYes
ConcertoYesYesYesYesYes
Service Works GlobalPartlyYesYesPartlyYes
MaintainXPartlyYesNot confirmedPartlyYes
SnapfixYesYesNot confirmedPartlyPartly

For the products ordered for this job, see the top FM compliance software, or read what planned preventive maintenance is.

Common questions

Does the law require quarterly fire door checks?

Only in England, and only for communal fire doors in buildings over 11 metres tall with two or more flats. Elsewhere fire doors must be kept maintained, but the law fixes no frequency.

How frequently should fire doors in a workplace be checked?

Government fire safety guidance recommends monthly checks of doors, seals and self-closers, and testing the release mechanisms on compartment doors and shutters every six months.

What does a fire door check involve?

Confirming that the door closes and latches, that its seals and strips are intact, that the hinges are secure, and that it has not been damaged or altered.

Other checks