Fire alarm testing and servicing: how often is it needed? (UK)

Check the panel each day, sound the alarm weekly from a different call point, and get a competent person to service the system roughly every six months. These come from BS 5839-1 recommendations and government guidance.

Every check and its frequency

Covers fire detection and alarm systems in premises within the Fire Safety Order in England and Wales. Domestic smoke alarms fall under a different standard.

CheckHow oftenBasisStatusSource
Check control and indicating equipment for faultsDaily (at least every 24 hours)Section 2.5 of the Home Office fire safety guide for offices and shops. This is guidance; under the Fire Safety Order the system must be maintained.Official guidanceFire safety risk assessment: offices and shops (Home Office guide, published 5 June 2006, last updated 12 September 2023, applies to England)
checked
Weekly alarm test (operate a different manual call point each week)WeeklyBS 5839-1 and section 2.5 of the Home Office fire safety guide recommend this. Test a different call point each week and note which one you used.British StandardFire safety risk assessment: offices and shops (Home Office guide, published 5 June 2006, last updated 12 September 2023, applies to England)
checked
Inspection and servicing by a competent personAbout every 6 months (any time 5 to 7 months after the last visit)BS 5839-1:2025 recommends this, as summarised by the Fire Industry Association. A visit falling anywhere from five to seven months after the previous one is acceptable.British StandardFire Industry Association: Guide to the changes in BS 5839-1:2025
checked

These intervals apply to non-domestic systems covered by BS 5839-1. Smoke alarms in homes come under a separate standard (BS 5839-6).

What it is about

A fire detection and alarm system picks up a fire through smoke or heat detectors, or when someone presses a manual call point, and alerts everyone in the building. Some systems also signal an alarm receiving centre, which then calls the fire service.

BS 5839-1, revised in 2025, is the code of practice for non-domestic buildings. Fire alarm contractors service systems against the test and service intervals it sets.

The checks one by one

Check control and indicating equipment for faults

Daily (at least every 24 hours) · Official guidance

Section 2.5 of the Home Office fire safety guide for offices and shops. This is guidance; under the Fire Safety Order the system must be maintained. Source, last checked .

Weekly alarm test (operate a different manual call point each week)

Weekly · British Standard

BS 5839-1 and section 2.5 of the Home Office fire safety guide recommend this. Test a different call point each week and note which one you used. Source, last checked .

Inspection and servicing by a competent person

About every 6 months (any time 5 to 7 months after the last visit) · British Standard

BS 5839-1:2025 recommends this, as summarised by the Fire Industry Association. A visit falling anywhere from five to seven months after the previous one is acceptable. Source, last checked .

Whose duty it is, and who can carry it out

Keeping the system maintained is the responsible person's duty. The Home Office guide recommends putting one person with sufficient authority and training in charge of testing. On-site staff usually carry out the weekly tests, while the six-monthly inspection and service should be done by a competent person, which in practice usually means a specialist fire alarm company.

What to record

The fire alarm log book should hold every weekly test (noting the call point used), every service visit, every false alarm and any faults. According to the Home Office guide, recording tests, false alarms and maintenance is good practice.

How to run it well

  1. Keep the weekly test to a fixed time, so occupants know a brief alarm is only a test.
  2. Work round the building using a different manual call point each week, so that each one gets tested in turn.
  3. Where the system is monitored, warn the alarm receiving centre beforehand and check afterwards that the signal was received.
  4. Investigate each false alarm; if they keep happening, the detectors or the system design need reviewing.
  5. Keep servicing on schedule: under BS 5839-1 a visit can fall anywhere from 5 to 7 months after the previous one.

Building types it applies to

Fire detection and alarm system is included in our compliance calendar for every building type we cover. Every calendar puts it next to the other checks that building usually needs.

Managing it in software

A CAFM system can schedule these checks, remind the person responsible, and file every certificate or log entry against the asset, keeping the evidence together for an inspector or insurer. The table sets out what each product states in its documentation.

SoftwareCompliance certificates and expiry trackingPlanned maintenance (PPM) schedulingSFG20 maintenance libraryContractor portalQR or NFC asset tags
JoblogicYesYesYesPartlyYes
InfraspeakYesYesYesYesYes
PlanonPartlyYesYesPartlyYes
ConcertoYesYesYesYesYes
Service Works GlobalPartlyYesYesPartlyYes
MaintainXPartlyYesNot confirmedPartlyYes
SnapfixYesYesNot confirmedPartlyPartly

For the products ordered for this job, see the top FM compliance software, or read what planned preventive maintenance is.

Common questions

How frequently does a fire alarm need testing?

Once a week, from a different call point each time, plus an inspection and service by a competent person roughly every six months.

Does the law require a weekly fire alarm test?

The legal duty is to keep the system maintained. Weekly testing is recommended by BS 5839-1, and following it is the normal way to demonstrate the system is maintained.

Are smoke alarms in homes covered by these frequencies?

No. Smoke alarms in homes fall under a different standard, BS 5839-6.

Who should carry out fire alarm servicing?

A competent person, defined in BS 5839-1 as suitably trained and qualified. In practice that usually means a specialist fire alarm company.

Other checks